FUEL COMSUMPTION CHART.  This chart is just an estimate of fuel consumption for diesel generators, and is to be used only as a reference point.  The exact gallons per hour will vary depending on various factors.

 
Generator Size
(kW)
1/4 Load
(gal/hr)
1/2 Load
(gal/hr)
3/4 Load
(gal/hr)
Full Load
(gal/hr)
20
0.6
0.9
1.3
1.6
30
1.3
1.8
2.4
2.9
40
1.6
2.3
3.2
4.0
60
1.8
2.9
3.8
4.8
75
2.4
3.4
4.6
6.1
100 
2.6
4.1
5.8
7.4
125 
3.1
5.0
7.1
9.1
135 
3.3
5.4
7.6
9.8
150 
3.6
5.9
8.4
10.9  
175 
4.1
6.8
9.7
12.7  
200 
4.7
7.7
11.0 
14.4  
230 
5.3
8.8
12.5 
16.6  
250 
5.7
9.5
13.6 
18.0  
300 
6.8
 11.3   
16.1 
21.5  
350 
7.9
 13.1   
18.7 
25.1  
400 
8.9
14.9  
21.3 
28.6  
500 
11.0 
18.5  
26.4 
35.7  
600 
13.2 
22.0  
31.5 
42.8  
750 
16.3 
27.4  
39.3 
53.4  
1000   
21.6 
36.4  
52.1 
71.1  
1250   
26.9 
45.3  
65.0 
88.8  
1500   
32.2 
54.3  
77.8 
106.5   
1750   
37.5 
63.2  
90.7 
124.2   
2000   
42.8 
72.2  
103.5  
141.9   
2250   
48.1 
81.1  
116.4  
159.6   

  
 
 

  
 
 

This estimated amperage chart is to be used as a guide only and is not an "exact" representation

80% Power Factor

kVa

kW

208V

220V

240V

380V

400V

440V

450V

480V

600V

2400V

3300V

4160V

6.3

8

17.5

16.5

15.2

9.6

9.1

8.3

8.1

7.6

6.1

 

 

 

9.4

7.5

26.1

24.7

22.6

14.3

13.6

12.3

12

11.3

9.1

 

 

 

12.5

10

34.7

33

30.1

19.2

18.2

16.6

16.2

15.1

12

 

 

 

18.7

15

52

49.5

45

28.8

27.3

24.9

24.4

22.5

18

 

 

 

25

20

69.5

66

60.2

38.4

36.4

33.2

30.1

24

6

4.4

3.5

 

31.3

25

87

82.5

75.5

48

45.5

41.5

40.5

37.8

30

7.5

5.5

4.4

37.5

30

104

99

90.3

57.6

54.6

49.8

48.7

45.2

36

9.1

6.6

5.2

50 

40

139

132

120

77

73

66.5

65

60

48

12.1

8.8

7

62.5

50

173

165

152

96

91

83

81

76

61

15.1

10.9

8.7

75

60

208

198

181

115

109

99.6

97.5

91

72

18.1

13.1

10.5

93.8

75

261

247

226

143

136

123

120

113

90

22.6

16.4

13

100

80

278

264

240

154

146

133

130

120

96

21.1

17.6

13.9

125

100

347

330

301

193

182

166

162

150

120

30

21.8

17.5

156

125

433

413

375

240

228

208

204

188

150

38

27.3

22

187

150

520

495

450

288

273

249

244

225

180

45

33

26

219

175

608

577

527

335

318

289

283

264

211

53

38

31

250

200

694

660

601

384

364

332

324

301

241

60

44

35

312

250

866

825

751

480

455

415

405

376

300

75

55

43

375

300

1040

990

903

576

546

498

487

451

361

90

66

52

438

350

1220

1155

1053

672

637

581

568

527

422

105

77

61

500

400

1390

1320

1203

770

730

665

650

602

481

120

88

69

625

500

1735

1650

1504

960

910

830

810

752

602

150

109

87

750

700

2430

2310

2104

1344

1274

1162

1136

1052

842

210

153

121

875

700

2430

2310

2104

1344

1274

1162

1136

1052

842

210

153

121

1000

800

2780

2640

2405

1540

1460

1330

1300

1203

962

241

176

139

1125

900

3120

2970

2709

1730

1640

1495

1460

1354

1082

271

197

156

1250

1000

3470

3300

3009

1920

1820

1660

1620

18504

1202

301

218

174

1563

1250

4350

4130

3765

2400

2280

2080

2040

1885

1503

376

273

218

1875

1500

5205

4950

5420

2880

2730

2490

2440

2260

1805

452

327

261

2188

1750

 

 

5280

3350

3180

2890

2830

2640

2106

528

380

304

2500

2000

 

 

6020

3840

3640

3320

3240

3015

2405

602

436

348

2812

2250

 

 

6780

4320

4095

3735

3645

3400

2710

678

491

392

3130

2500

 

 

7520

4800

4560

4160

4080

3765

3005

752

546

435

3750

3000

 

 

9040

5760

5460

4980

4880

4525

3610

904

654

522

4375

3500

 

 

10550

6700

6350

5780

5660

5285

4220

1055

760

610

 


 

 

 

 

 

TWO COMMON TYPES OF GENERATORS
SYNCHRONOUS VS INDUCTION

There are two commonly used types of generators. They are synchronous and induction. A synchronous generator, mainly used as an emergency powersource, and often times used as the sole source of all power requirements in a inany giving area. When the generator is used as the sole power source, it must belarge enough, that is, the KVA / KW rating must exceed the demand by no lessthan 20% to handle the high peak loads of the operation. In addition, switchgearand paralleling equipment is often installed for simultaneously operating thegenerator with the utility.

Induction generators are used as peak saving options. Induction generators provide power to withstand additional loads or demands such as air-conditioningin the hot months of the year and for starting large machinery, etc.  induction generators produce power only from a parallel power source, such as anothergenerator or the local utility provider. Induction generators cannot operateindependently of another power source, therefore it’s beneficial to work with the local utility provider to gauge the operations peak KW demands to help in sizingthe induction generator. There are several factors that need to be consideredbefore purchasing a generator such as, the transfer switch size, additional fueltank requirements, enclosure options and fuel consumption.

If you are in need of a synchronous or induction generator, give Vital Power and Equipment call and we will assist you in sizing your generator(s) and provide you with the best possible solution to your back up, standby, or prime power needs.

Call Us Today (208) 209-5702

HOME  | COMPANY NEWS  | ABOUT US  | TOOLS & INFO  | INVENTORY  | BUY  | SELL  | CONTACT US  | SITE MAP  | LINKS  | GLOSSARY
Privacy Statement Terms Of Use Login
Copyright Vital Power & Equipment Designed by WSI